822,00 EUR
incl. 23% Tax plus shipping

Halmburger, WRL-K-75 UP Decentralized ventilation unit with HRU
[WRL-K 75]


  • Click to enlarge
  • Click to enlarge
  • Click to enlarge
WRL-K-75 Decentralized ventilation unit with heat recovery unit - Flush version

  • Type / Dimensions (H × W × D)
  • Product number: 2000
    WRL-K 75 Flush-mounted: 623 × 347 × 85 mm
    WRL-K 75 Surface-mounted: 623 × 347 × 207 mm
  • Color
    - Ventilator: white (standard), other colors on request
    - Ventilation grilles: gray
    - Multifunctional control: white
  • Air consumption Permanent ventilation levels 12 - 20 - 30 - 45 m³ / h
  • Heat recovery level in the above
    - Continuous ventilation (corrected value for DIBt)
    79 - 74 - 68 - 65%
  • Heat recovery level in the above
    - Permanent ventilation stages (TUV metrics)
    85 - 79 - 72 - 69%
  • Power consumption at the above continuous ventilation levels 3.6 - 4.8 - 6.8 - 12.6 W
  • Air capacity Intensive ventilation 60 m? / h, duration freely selectable for 10 min ... 9 h 50 min
  • Power consumption for intensive ventilation 20.7 W
  • Summer ventilation time freely selectable for 10 min ... 9 h 50 min
  • Exhaust air ventilation duration freely selectable for 10 min ... 9 h 50 min
  • Power consumption internal frost protection 0.9 W
  • Power consumption Optional ventilation grid heating 6.0 W
  • Operating voltage / frequency 230 V AC, 50 / 60Hz
  • Sound pressure level at air output 12 m? / h approx. 17.2 dB (A)
  • Rated noise reduction with open air dampers approx. 31.0 dB
  • Rated noise reduction with closed air dampers approx. 32.0 dB
  • Filter inlet / exhaust air (standard) M5
  • Filter supply air (optional) F7 or activated carbon filter G3
  • Protection class IP24 (Mounting: manufacturer side up to maximum permitted in protection area II)
  • Protection B 16 A
  • Building material class B2
  • FI protection circuit 30 mA
  • Outside and exhaust air pipes DN 75, length 600 mm
  • Supply and exhaust fans Centrifugal fan 24 V DC, single-inlet
  • Supply line NYM 3G1,5 mm²
  • Heat exchanger cross-current heat exchanger
  • Filter change indicator yes
  • Frost protection yes
  • Function monitoring with fault indication yes
  • Automated drainage of condensation yes
  • Operating hours counter yes
  • Automatic air flap control yes




  • => FILM (DE)

    Reviews
    Manufacturers
    Quick Find
     
    Use keywords to find the product you are looking for.
    Advanced Search
    Show mobile view

    0 items
    Share Product
    Share via E-Mail Share on Facebook Share on Twitter Share on Google Buzz Share on Digg
    Languages
    German Polish English
    Currencies

    Enter your shipping information.